Off-gridIP20
Off-grid inverter 6 kW
DLXN-BIN-S-I-6KW
Dual AC outputs with a dedicated smart-load port, built-in ATS for generator transfer, up to 9 units in parallel. Built for sites with no grid at all.
- Rated output
- 6 kW / 6 kVA
- Phases
- Single-phase 230 V
- Max PV input
- 8 kW (2 × 4 kW MPPT)
- MPPT
- 65–450 Vdc · 16 A
- Battery
- 48 Vdc · 100 A charge
Full specifications
| AC Output | |
|---|---|
| Rated Power | 6kVA/6kW |
| Surge Power | 12kW/12kVA |
| AC Output Voltage | 208/220/230/240Vac(Settable) |
| Rated AC Output Frequency | 50/60Hz |
| Max Inverter Efficiency | 94% |
| Transfer Time | <20ms@Single, <30ms @ Parallel |
| output waveform | Pure Sine Wave |
| Power Factor | 1 |
| No-Load Loss | <45W@Rate Voltage |
| PV Input | |
| Number Of MPP Trackers | 2 |
| Max PV Input Power | 4000W*2 |
| Max PV Array Open Circuit Voltage | 500Vdc |
| Max PV Input Current | 16A *2 |
| Startup Voltage | 100Vdc±10Vdc |
| MPPT Voltage Range | 65Vdc-450Vdc |
| MPPT Charging Efficiency | 99% |
| Battery | |
| compatible battery types | Lead-acid,Lithium battery |
| MPPT Voltage Range | 65Vdc-450Vdc |
| MPPT Charging Efficiency | 99% |
| Compatible Battery Types | Lead-acid,Lithium battery |
| Rated Battery Voltage | 48Vdc |
| Battery Voltage Range | 40Vdc-60Vdc |
| Minimum Cold Start Battery Voltage | 46Vdc |
| Max Solar Charging Current | 100A |
| Max AC Charging Current | 80A |
| Max Charging Current(PV+AC) | 100A |
| Activate The Lithium Battery Function | PV / AC |
| Mechanical Specifications | |
| Inverter Dimensions | 391*345*131mm |
| Packing Measurements | 475*440*203mm |
| Net Weight | 9.8kg |
| Gross Weight | 11.2kg |
| Monitoring Option | WiFi Module |
| Environment | |
| Protection Degree | IP20 |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) |
| Altitude | <2000 Meters |
| Operating Temperature | -10℃~50℃ |
| Storage Temperature | -15℃~60℃ |
| Noise | <60dB |
| Certificate | CE |