Voltage Drop & Cable Size Calculator
The number engineers check first — keep DC drop under 3% and total drop under 5%.
Voltage drop
1.31V
Voltage drop
2.73%
Voltage at load
46.69V
Result
PASS (limit 3%)
ΔV = 2 × I × L × ρ ÷ A for DC and single-phase (the 2 is the return path); × √3 for three-phase. ρ copper = 0.0175, aluminium = 0.0282 Ω·mm²/m at 20 °C. Limits: DC 3%, AC single-phase 3%, three-phase 5%. Check ampacity separately — a cable can pass voltage drop and still overheat.